Intermatic Home Settings Three-Way In-Wall Dimmer Switch #HA20C Owners Manuals, User Guides, Instructional Help Documents & Operating Information - T100-Specifications-EN.pdf
Citation
T100 Series
Electromechanical Time Switches Project: Location:
T100 Series
Product Type:
The T100 Series Mechanical Time Switches are heavy-duty switches that have the highest horsepower ratings in the industry for industrial, commercial and residential applications.
Contact/Phone: Model #:
Features
• Provides direct 24-Hour control of most loads • Control electrical loads up to 40 Amps • 1 to 12 ON/OFF operations each day • Minimum ON/OFF times of 1 hour • Manual override • All models equipped with one ON and one OFF tripper
Ratings
Enclosure Type:
See table
Knockouts: Combination 1⁄2"- 3⁄4" nominal knockouts, one on back and on each side, and two on bottom Switch Type:
T101R
See table
Switch Rating: Each Pole 40 Amp Resistive, 120-480 VAC 40 Amp Tungsten, Inductive or 1000 VA Pilot Duty, 120-277 VAC 2 HP (24 FLA) 120 VAC 5 HP (28 FLA) 240 VAC single-phase Power Input:
3 W Maximum
Operating Temperature:
-40°F to 130°F (-40°C to 54°C)
T104PCD82
Shipping Weight: Type 1 - 3 lbs. (1.4 kg) Type 3R - 4 lbs. (1.8 kg) Warranty:
Limited 1 year
T101 Model with Type 1 Steel Enclosure
Model with Type 3R Steel Enclosure
Model with Type 3R Plastic Enclosure
Model with Plastic Type 3R Enclosure with See Through Cover
Switch Type
Clock Motor Volts
Hz
Amps/ Pole
HP Rating
T101
T101R
T101P
T101PCD82
SPST
125
60
40
2
T102
T102R
T102P
-
SPST
208-277
60
40
5
T103
T103R
T103P
T103PCD82
DPST
125
60
40
2
T104
T104R
T104P
T104PCD82
DPST
208-277
60
40
5
T104-50
-
-
-
DPST
208-277
50
40
5
T101B**
-
-
-
SPST
125
60
40
2
T105
-
-
-
1NO/1NC*
125
60
40
2
N/A
T106R
-
-
1NO/1NC*
208-277
60
40
5
*Can be wired SPDT **Separate Clock Motor Terminals Energy Controls
T100 Series Specification
The time switch shall be of the 24-Hour dial type, capable of permitting up to 12 ON/OFF operations each day. The time switch shall provide a minimum ON/OFF time of 1 hour. The time switch shall be powered by ____________ (125)(208277) VAC,_________ (50)(60) Hz power supply. The time switch motor shall be a synchronous motor, which shall be designed to withstand a minimum of 6000 volt transients. The time switch motor shall be connected to the supply terminals with ring-type connectors and shall not require more than 3 Watts to operate the time switch. The time switch mechanism shall be a snap-in design to provide ease of mechanism removal from the enclosure. The time switch enclosure shall be a _______________(Type 1 steel)(Type 3R steel)(Type 3R plastic with see through cover) lockable enclosure. The time switch enclosure shall provide a minimum of 31 cubic inches of wiring space and provide a nonremovable cover, which shall swing open a full 180 degrees. The time switch shall provide clear terminal identification on a see-through non-curling terminal insulator. A visual indicator shall be provided in the time switch for inspecting clock motor operation. The time switch contact blades shall be a one piece design with welded silver alloy contacts and shall be designed to provide wiping action on contacts during operation to ensure reliable load switching. Terminal connections shall be made using teeter-type terminal screws to provide secure connections for wire sizes up to #8 AWG. Switch configuration shall be ______________ (SPST)(DPST) (1NO/1NC) with a switch rating each pole: • 40 Amp Resistive, 120-480 VAC • 40 Amp Tungsten, Inductive or 1000 VA Pilot Duty each pole, 120-277 VAC • 2 HP (24 FLA), 120 VAC • 5 HP (28 FLA), 240 VAC The time switch shall be Agency Listed under Clock Operated Switches and shall be Intermatic model ________________ (See Model Numbers Listed).
Diagrams Clock Motor
Equipment Ground
Clock Motor
Equipment Ground
A
1
A
2
A
120 VAC Input
Line
To Load
208-277 VAC Input
3
To Load
Line 2
120 VAC Input
3"
[7.62 cm]
Jumper
A
1
2
3
4
208-277 VAC Input Neutral*/Line 1**
Line
7 ¾"
Energy Controls
To Loads
Clock Motor
4
To N.0. Load Model T105 (1 NO/1NC)
5" [12.70 cm]
3
Neutral
Jumper See Note 3
*2