IT-100 v1.0 Integration Module

Module d’intégration IT-100 v1.0

Installation Instructions

Instructions d’installation

The IT-100 Integration Module can be used to quickly and easily communicate with PowerSeries™ panels through a standard RS-232 serial connection (see the IT-100 Developer’s Guide for more information on communicating with the IT-100 module) at www.dsc.com/support/installation manuals.

Le module d’intégration IT-100 peut être utilisé pour se communiquer rapidement et facilement avec les tableaux PowerSeries™ à travers d’une connexion serial RS-232 standard (voir le Guide du Développeur IT-100 pour plus d’informations sur la communication avec le module IT-100) à l’adresse www.dsc.com/support/installation manuals.

El módulo de Integración IT-100 puede utilizarse para comunicarse rápida y fácilmente con los paneles PowerSeries™ a través de una conexión serial RS-232 estándar (ver la Guía del Desarrollador IT-100 para mayores informaciones sobre la comunicación con el módulo IT-100) en www.dsc.com/support/installation manuals.

Specifications

Spécifications

Consumo de Corriente del Módulo: 80 mA

Consommation en Courant du Module: 80 mA

Terminal Connections

Conexiones del Terminal

Connexion du Terminal

KEYBUS - The 4-wire KEYBUS connection is used by the panel to

KEYBUS - La connexion KEYBUS de 4 fils est utilisée par le tableau

KEYBUS - La conexión KEYBUS de 4 hilos es utilizada por el panel para comunicarse con el módulo. Conecte los terminales RED (ROJO), BLK (NEGRO), YEL (AMARILLO) y GRN (VERDE) a los terminales KEYBUS en un panel PowerSeriesTM. DB9 – Requiere un cable RS-232 recto. Solamente las conexiones RX, TX y GND son utilizadas.

Module Current Draw: 80 mA

communicate with the module. Connect the RED, BLK, YEL and GRN terminals to the KEYBUS terminals on a PowerSeries™ panel. DB9 – Requires a “straight-through” RS-232 cable. Only the RX, TX and GND connections are used.

To Connect Module to a Control Panel This module should be installed in one of the following enclosures: PC4003C, PC5003C, HS-CAB1000, HS-CAB3000, HS-CAB4000 (see Fig. A). 1. Connect module to the KEYBUS (with the panel powered down). If using a ferrite please refer to Fig. B. 2. Connect the IT-100 Integration Module via an RS-232 cable to a third party system, located in the same room and no more than 98.4ft (30m) from the IT-100. 3. Power up the system.

NOTES: • •

The IT-100 is intended to be installed by qualified service personnel only. These instructions shall be used in conjunction with the applicable Installation Instructions of the associated PowerSeries™ control panel.

Baud Rate Selection Default rate is set at 9600 Baud Rate. Please refer to Table 1 for recommended baud rate settings per cable length. To change Baud rate in normal operation refer to the IT-100 Developer's Guide ("Baud Rate Change" command). To reset Baud rate to default follow these steps: 1. Disconnect Keybus cable (if connected to Keybus). 2. Using a wire, connect the DB9 connector's pins 2 and 3. 3. Connect Keybus cable and wait for the LED to start flashing. 4. Remove wire connecting the DB9 connector's pins 2 and 3. Baud rate is now reset to default (9,600 Baud).

pour se communiquer avec le module. Connectez les bornes RED (ROUGE), BLK (NOIR), YEL (JAUNE) et GRN (VERT) aux bornes KEYBUS sur un tableau PowerSeriesTM. DB9 – Exige un câble RS-232 droit. Uniquement les connexions RX, TX et GND sont utilisées.

Pour Connecter le Module à un Tableau de Contrôle Ce module doit être installé dans les boîtes de protection suivantes: PC4003C, PC5003C, HS-CAB1000, HS-CAB3000, HS-CAB4000 (Fig. A). 1. Connectez le module au KEYBUS (avec le tableau débranché). Si utilisant une ferrite, se référer au Fig. B. 2. Connectez le module d’intégration IT-100 à travers d’un câble RS-232 au système d’un autre fabricant (localisé dans la même salle et à une distance maximale de 30m (98.4 pi) du module IT-100). 3. Branchez le système.

Módulo de Integración IT-100 v1.0 Instrucciones de Instalación

Especificaciones

Para Conectar el Módulo a un Panel de Con